Cover
Technical Instructions for
Configuring an ISO-on-TCP
Connection
S7-300 / S7-400 Industrial Ethernet CPs
FAQ January 2011
Service & Support
Answers for industry.Question
This entry is from the Service&Support portal of Siemens AG, Sector Industry,
Industry Automation and Drive Technologies. The general terms of use
(http://www.siemens.com/terms_of_use) apply.
Clicking the link below directly displays the download page of this document.
http://support.automation.siemens.com/WW/view/en/47885440
Question
How do you configure an ISO-on-TCP connection for data exchange between S7-
300 and / or S7-400 over Industrial Ethernet CPs?
Answer
The instructions and notes listed in this document provide a detailed answer to this
question.
Technical instructions on configuring an ISO-on-TCP connection
V1.0 , Entry ID: How do you configure an ISO-on-TCP connection for data exchange between S7-300 and/or S7-
2 400 over Industrial Ethernet CPs?Table of Contents
Table of Contents
1 Introduction........................................................................................................4
2 Configuration.....................................................................................................5
2.1 Configuring CP343-1 and CP443-1 Advanced....................................5
2.1.1 Assigning IP addresses to CP343-1 and CP443-1 Advanced.............5
2.1.2 Entering the IP address of CP343-1 in the Hardware Configuration
and downloading the configuration into the CPU.................................8
2.1.3 Entering the IP address of CP443-1 Advanced in the Hardware
Configuration and downloading the configuration into the CPU........10
2.2 Configuring an ISO-on-TCP Connection............................................13
2.2.1 Configuring specified ISO-on-TCP connections................................13
2.2.2 Configuring unspecified ISO-on-TCP connections............................17
Technical instructions on configuring an ISO-on-TCP connection
V1.0 , Entry ID: How do you configure an ISO-on-TCP connection for data exchange between S7-300 and/or
S7-400 over Industrial Ethernet CPs? 31 Introduction
1 Introduction
You can use the open communication through ISO-on-TCP connections for data
exchange by way of the Industrial Ethernet CPs of S7-300 and S7-400.
In this example an S7-300 is connected over the PROFINET interface of the
CP343-1 on the subnetwork 172.16.0.0. The S7-400 on the other hand is
connected over the GBIT interface of the CP443-1 Advanced on the subnetwork
172.16.0.0. The PROFINET interface of the CP443-1 Advanced is connected on
the subnetwork 192.168.99.0.
Configuration overview
Figure 1-1 shows an overview of the configuration.
Figure 1-1
S7-300 S7-400
Technical instructions on configuring an ISO-on-TCP connection
V1.0 , Entry ID: How do you configure an ISO-on-TCP connection for data exchange between S7-300 and/or S7-
4 400 over Industrial Ethernet CPs?
CP343-1
CP443-1
Advanced
IP address PROFINET interface:
ISO-on-TCPconnection
192.168.99.121
subnet mask: 255.255.255.0
IP address: 172.16.43.2 IP address Gigabit interface:
subnet mask: 255.255.0.0 172.16.49.99
subnet mask: 255.255.0.0
SCALALANCE X2 Configuration
2 Configuration
Below we describe how to configure an ISO-on-TCP connection for sending and
receiving data by way of an Industrial Ethernet CP of S7-300 and S7-400.
2.1 Configuring CP343-1 and CP443-1 Advanced
2.1.1 Assigning IP addresses to CP343-1 and CP443-1 Advanced
The following IP addresses are used in this configuration.
Table 2-1
Industrial Ethernet CP Interface IP address Subnet mask
CP343-1 PROFINET 172.16.43.2 255.255.0.0
CP443-1 Advanced PROFINET 192.168.99.121 255.255.255.0
CP443-1 Advanced GBIT 172.16.49.99 255.255.0.0
Assign the IP addresses to CP343-1 and CP443-1 Advanced.
Follow the instructions below for assigning the IP addresses.
Technical instructions on configuring an ISO-on-TCP connection
V1.0 , Entry ID: How do you configure an ISO-on-TCP connection for data exchange between S7-300 and/or
S7-400 over Industrial Ethernet CPs? 52 Configuration
Table 2-2
No. Configuration step Note
1. Connect the SIMATIC Field PG on
which the configuration created with
STEP 7 is stored to the PROFINET
interface of CP343-1.
In Windows network settings
LAN (Local Area Network) of the
SIMATIC Field PG you enter an IP
address that is in the same
subnetwork as that of CP343-1.
In this example the IP address
172.16.43.100 and subnetwork mask
255.255.0.0 are used for the
SIMATIC Field PG.
2. In the SIMATIC Manager you open
the STEP 7 project that contains the
configurations of S7-300 and S7-400
between which the data is to be
exchanged over an ISO-on-TCP
Technical Instructions for
Configuring an ISO-on-TCP
Connection
S7-300 / S7-400 Industrial Ethernet CPs
FAQ January 2011
Service & Support
Answers for industry.Question
This entry is from the Service&Support portal of Siemens AG, Sector Industry,
Industry Automation and Drive Technologies. The general terms of use
(http://www.siemens.com/terms_of_use) apply.
Clicking the link below directly displays the download page of this document.
http://support.automation.siemens.com/WW/view/en/47885440
Question
How do you configure an ISO-on-TCP connection for data exchange between S7-
300 and / or S7-400 over Industrial Ethernet CPs?
Answer
The instructions and notes listed in this document provide a detailed answer to this
question.
Technical instructions on configuring an ISO-on-TCP connection
V1.0 , Entry ID: How do you configure an ISO-on-TCP connection for data exchange between S7-300 and/or S7-
2 400 over Industrial Ethernet CPs?Table of Contents
Table of Contents
1 Introduction........................................................................................................4
2 Configuration.....................................................................................................5
2.1 Configuring CP343-1 and CP443-1 Advanced....................................5
2.1.1 Assigning IP addresses to CP343-1 and CP443-1 Advanced.............5
2.1.2 Entering the IP address of CP343-1 in the Hardware Configuration
and downloading the configuration into the CPU.................................8
2.1.3 Entering the IP address of CP443-1 Advanced in the Hardware
Configuration and downloading the configuration into the CPU........10
2.2 Configuring an ISO-on-TCP Connection............................................13
2.2.1 Configuring specified ISO-on-TCP connections................................13
2.2.2 Configuring unspecified ISO-on-TCP connections............................17
Technical instructions on configuring an ISO-on-TCP connection
V1.0 , Entry ID: How do you configure an ISO-on-TCP connection for data exchange between S7-300 and/or
S7-400 over Industrial Ethernet CPs? 31 Introduction
1 Introduction
You can use the open communication through ISO-on-TCP connections for data
exchange by way of the Industrial Ethernet CPs of S7-300 and S7-400.
In this example an S7-300 is connected over the PROFINET interface of the
CP343-1 on the subnetwork 172.16.0.0. The S7-400 on the other hand is
connected over the GBIT interface of the CP443-1 Advanced on the subnetwork
172.16.0.0. The PROFINET interface of the CP443-1 Advanced is connected on
the subnetwork 192.168.99.0.
Configuration overview
Figure 1-1 shows an overview of the configuration.
Figure 1-1
S7-300 S7-400
Technical instructions on configuring an ISO-on-TCP connection
V1.0 , Entry ID: How do you configure an ISO-on-TCP connection for data exchange between S7-300 and/or S7-
4 400 over Industrial Ethernet CPs?
CP343-1
CP443-1
Advanced
IP address PROFINET interface:
ISO-on-TCPconnection
192.168.99.121
subnet mask: 255.255.255.0
IP address: 172.16.43.2 IP address Gigabit interface:
subnet mask: 255.255.0.0 172.16.49.99
subnet mask: 255.255.0.0
SCALALANCE X2 Configuration
2 Configuration
Below we describe how to configure an ISO-on-TCP connection for sending and
receiving data by way of an Industrial Ethernet CP of S7-300 and S7-400.
2.1 Configuring CP343-1 and CP443-1 Advanced
2.1.1 Assigning IP addresses to CP343-1 and CP443-1 Advanced
The following IP addresses are used in this configuration.
Table 2-1
Industrial Ethernet CP Interface IP address Subnet mask
CP343-1 PROFINET 172.16.43.2 255.255.0.0
CP443-1 Advanced PROFINET 192.168.99.121 255.255.255.0
CP443-1 Advanced GBIT 172.16.49.99 255.255.0.0
Assign the IP addresses to CP343-1 and CP443-1 Advanced.
Follow the instructions below for assigning the IP addresses.
Technical instructions on configuring an ISO-on-TCP connection
V1.0 , Entry ID: How do you configure an ISO-on-TCP connection for data exchange between S7-300 and/or
S7-400 over Industrial Ethernet CPs? 52 Configuration
Table 2-2
No. Configuration step Note
1. Connect the SIMATIC Field PG on
which the configuration created with
STEP 7 is stored to the PROFINET
interface of CP343-1.
In Windows network settings
LAN (Local Area Network) of the
SIMATIC Field PG you enter an IP
address that is in the same
subnetwork as that of CP343-1.
In this example the IP address
172.16.43.100 and subnetwork mask
255.255.0.0 are used for the
SIMATIC Field PG.
2. In the SIMATIC Manager you open
the STEP 7 project that contains the
configurations of S7-300 and S7-400
between which the data is to be
exchanged over an ISO-on-TCP